How To Calibrate I/P converter / Calibration Procedure for I/P converter.
Types of equipment required:-
- I/P converter,
- Milliamp source,
- Pressure source(20 psi).
- Master gauge.
The procedure of I/P converter online Calibration:-
- Remove the I/P from the process.
- If there is any top cover in I/P remove it.
- Connect 20-psi supply pressure and connect a milliamp source to the I/P.
- Set the input signal to 4 mA and check the output pressure on gauge as 3 psi.
- If the pressure is showing more or less than 3 psi then adjust zero.
- Turn zero adjustment screw slowly by very small turn to obtain 3-psi pressure. More turning of zero adjustment may damage the I/P converter. Counterclockwise rotation increases the pressure, and clockwise rotation decreases the pressure.
- Set the input current signal to 20 mA and check the output pressure on gauge as 15 psi.
- Turn the span adjustment potentiometer very slowly by small turn to obtain 15-psi pressure. More turning of span adjustment may damage the I/P converter.
- Repeat step 4 to check that the desired low value (4 ma ~ 3 psi) has not changed after adjusting the span. If necessary repeat from steps 3
- Reconnect the I/P in the process.