How To Calibrate P/I converter./Procedure for P/I converter Calibration.
Equipments required:-
- Supply voltage 24vdc,
- Pressure source(handheld test pump),
- Multimeter.
Procedure for P/I converter Bench Calibration.:-
- Set digital calibrator on measure mode.
- Connect input signal i.e. 3-15 psig.
- Set the input signal to 3 psi and check the output current as 4 mA.
- If the current is showing more or less than 4 mA then adjust zero pot to make output 4ma.
- Set the input pressure signal to 15 psi and check the output current 20 mA.
- Turn the span adjustment potentiometer on Converter and adjust 100%.
- Repeat step 3 to check that the desired low value (3 psi ~ 4mA) has not changed after adjusting the span.
How To Calibrate P/I converter.