How To Calibrate Pressure Transmitter.
How To Calibrate Pressure Transmitter./ Procedure for Pressure Transmitter Calibration.
Types of equipment required:-
- Pressure transmitter
- Multimeter
- HART communicator
- Handheld test pump (pressure source).
Procedure OF Pressure Transmitter online calibration:-
- Isolate the Pressure Transmitter from the Process.
- Slowly open the vent plug and the vent valve to release the pressure.
- Connect the multimeter with the transmitter and ensure that output is4ma when 0% pressure is applied.
- Connect the handheld test pump (pressure source) to the transmitter.
- Ensure there is no leak.
- Apply pressure range at 0%, 25%, 50%, 75%, and 100% and check
- there is an error.
- If there is any error calibration should be done.
If the transmitter is an analog transmitter
- Apply 0% pressure as per LRV with handheld test pump and check multimeter if it is not 4ma adjust the zero pot in the transmitter and correct transmitter output to 4ma
- Apply 100%pressure as per the URV and correct 20ma in multimeter by adjusting span pot in the transmitter
- NOTE: Repeat these steps to rectify the error.
In case of SMART Transmitter
We have to use HARTcommunicator.Connect the communicator with the transmitter select the HART Communicator Menu for lower-range value trim and upper range value trim using the below steps.
- HART communicator will automatically calibrate the transmitter.
- Restore the process connection
- Take the transmitter on line. Ensure there is no leak.
For an example of five-point calibration is given below:-
Low range value = 0psi
Upper range value = 200psi
PERCENTAGE OF RANGE(%)
|
INPUT PRESSURE
|
OUT PUT CURRENT (IDEAL)
|
0%
|
0 PSI
|
4.00 mA
|
25%
|
50 PSI
|
8.00 mA
|
50%
|
100 PSI
|
12.00 mA
|
75%
|
150 PSI
|
16.00 mA
|
100%
|
200 PSI
|
20.00 mA
|
75%
|
150 PSI
|
16.00 mA
|
50%
|
100 PSI
|
12.00 mA
|
25%
|
50 PSI
|
8.00 mA
|
0%
|
0 PSI
|
4.00 mA
|